2022 Recall (Most Relevant — Actual QO Load Centers)
-
Recall date: June 16, 2022 (DHSES NY, Fox 17)dhses.ny+1
-
Product: Square D QO Plug-On-Neutral (PON) Load Centers — indoor and outdoor breaker boxes/panels
-
Units affected: About 1.4 million in the US (plus 289,000 in Canada)
-
Manufacture window: February 1, 2020 through January 12, 2022, made at Schneider Electric Plant 15 only
-
Date codes: 200561 through 220233 (format YYWWDS)
-
Defect: A loose neutral screw connection on the plug-on-neutral bar that wasn’t torqued properly, which can cause the load center to overheat — thermal burn and fire hazard (AudioShark forum citing Schneider, Yukon government bulletin)yukon+1
-
Note for field verification: Panels with date codes before January 13, 2022 that were validated during Schneider’s containment process carry a green dot on the carton — those are excluded from the recallabihomeservices
-
This recall does not apply to Square D’s cheaper Homeline series — QO onlyabihomeservices
Earlier Related Recalls (Worth Knowing, Different Products)
-
August 2010: Counterfeit “Square D”/”SQD” branded QO breakers (not genuine Square D product) recalled by distributor Miami Breaker Inc. — models QO115, QO120, QO130, QO215, QO220, QO230, QO240, QO250, QO260, sold March 2005–July 2006. These fail to trip under overload. Genuine Square D QO breakers have the amp rating painted on the handle, the Square D insignia molded into the side, and a yellow chromate clip — anything not matching that description is suspect.cpsc
-
March 2014: A recall of genuine Square D FA, FH, FI, FY, and KI breakers (not QO) manufactured May–June 2013, date codes 13193–13255, for failing to trip under overload.everestglobal
For field use, the panel’s date code is printed on the label inside the door or cover — that’s what you’d check against the 200561–220233 range for the 2022 recall.