Suction Line (Low Side, large/insulated) Temperature
- Normal operating range: The suction line temperature measured about 6–12 inches from the compressor inlet should typically be between 40°F and 60°F under normal running conditions[1][2][3].
- Absolute minimum: The suction temperature should never drop below 35°F entering the compressor, as this risks freezing the evaporator coil and returning liquid refrigerant to the compressor, which can cause serious damage[3][4].
- Typical “good” value: Most systems aim for a temperature safely above freezing, ideally in the 40°F to 60°F range, with a superheat (temperature of vapor above its boiling point at that pressure) of about 20°F to 30°F being ideal[1][2].
- If a liquid-to-suction line heat exchanger is installed, suction line temperatures up to 65°F at the compressor inlet are still acceptable[1].
“Suction line temperature…should be somewhere in the range of 40° to 60°. …If a liquid line/suction line heat exchanger is installed, a suction line temperature of 65° at the inlet of the compressor is acceptable. Air temperature leaving the evaporator should be 37° to 41°.”[1]
Liquid Line (High Side) Temperature
- Relative minimum: The liquid line temperature should not be below outdoor ambient temperature. A significantly colder liquid line may indicate a restriction or sensing issue[5][6].
- Normal “approach”: Typically, the liquid line temperature should be 4–15°F above the outdoor ambient temperature in normal operation[6].
- If the liquid line is colder than the ambient air, check for restrictions or measurement errors[5][6].
“The liquid line can’t be any colder than the medium (outdoor air) to which the condenser is rejecting its heat in a traditional residential split A/C unit. … The temperature should be between 4 and 15 degrees warmer than the outdoor temperature.”[5][6]
Additional Notes
- Evaporator coil freeze protection: The evaporator coil temperature must stay above 32°F to prevent freezing, so suction line temperatures below this point are never acceptable for standard air conditioning[1][3].
- Operating conditions, system design, refrigerant type, and ambient temperatures will influence these values—always consult manufacturer specifications for final guidance.
Summary Table: Minimum Acceptable AC Refrigerant Line Temperatures
Line Type | Minimum Acceptable Temp | Normal Range | Notes |
Suction Line | 35°F (never below) | 40–60°F | 65°F max if heat exchanger installed |
Liquid Line | Not below ambient temp | 4–15°F above ambient | Colder indicates problem or measurement error |
Failing to stay within these ranges can result in poor performance or system damage, particularly to the compressor on the suction side[1][3][4].
⁂
- https://s3.amazonaws.com/system-evaluation-manual-17-2/Sample_1_14_2017.pdf
- https://www.reddit.com/r/HVAC/comments/8k9uj1/refrigerant_line_maxmin_temperature/
- https://www.contractingbusiness.com/service/media-gallery/20870989/testing-refrigerant-charge-without-gauges
- https://www.inspectorsjournal.com/topic/3365-cold-high-pressure-line/
- https://www.youtube.com/watch?v=XClJ74NQx20
- http://www.hvacrschool.com/podcasts/short-89-liquid-line-temperature-2/